| Products
More than 20 years of R&D Experience
SMC-C switchover capacitor contactor can switch over 3-phase single or multiple stage capacitor bank.
In conformity with IEC69047-4-1.
Operation Parameter:
Operating Times | SMC-9C,12C,18C,22C,32C,40C | 240 times/h |
SMC-50C,65C,75C,85C,100C | 100 times/h | |
Electrical Endurance | SMC-9C,12C,18C,22C,32C,40C,48C | 200,000 times |
SMC-50C,65C,75C,85C,100C | 100,000 times |
Technical Parameters:
TYPE | Rated Current(A) | Maximum Operating Power (kVar) | Applied Unit | ||
200-240V | 400-440V | 550-600V | |||
SMC-9C | 14 | 5 | 9.7 | 14 | SAC-9 |
SMC-12C | 18 | 6.7 | 12.5 | 18 | SAC-9 |
SMC-18C | 24 | 8.5 | 16.7 | 24 | SAC-9 |
SMC-22C | 26 | 10 | 18 | 26 | SAC-9 |
SMC-32C | 36 | 15 | 25 | 36 | SAC-9 |
SMC-40C | 48 | 20 | 33.3 | 48 | SAC-9 |
SMC-50C | 58 | 22 | 40 | 58 | SAC-50 |
SMC-65C | 66 | 25 | 45.7 | 66 | SAC-50 |
SMC-75C | 78 | 29.7 | 54 | 78 | SAC-50 |
SMC-85C | 92 | 35 | 60 | 92 | SAC-50 |
SMC-100C | 94 | 37 | 62 | 94 | SAC-50 |
Capacitor Unit Technical Parameter:
Type | Contactor | Maximum Operating Power (kVar) | Rated Current | ||
200-240V | 400-440V | 550-600V | |||
SAC-9 | SMC-9 | 5 | 9.7 | 14 | 14 |
SMC-12 | 6.7 | 12.5 | 18 | 18 | |
SMC-18 | 8.5 | 16.7 | 24 | 24 | |
SMC-22 | 10 | 18 | 26 | 26 | |
SMC-32 | 15 | 25 | 36 | 36 | |
SMC-40 | 20 | 33.3 | 48 | 48 | |
SAC-50 | SMC-50 | 22 | 40 | 58 | 58 |
SMC-65 | 25 | 45.7 | 66 | 66 | |
SMC-75 | 29.7 | 54 | 78 | 78 | |
SMC-85 | 35 | 60 | 92 | 92 | |
SMC-100 | 37 | 62 | 94 | 94 |
Note:
● When the switch is closed,condenser must be discharged before recharged.(Maximum residual voltage at terminals≤50V)
● To prevent short current,gG type fuse must be 1.5~2 times than rated current.
Dimensions(mm):